|
TABLE OF CONTENTS
Section
Page
Description of Capabilities and
Functions.
2
Modes of
Operation
3
a)
Local
3
b) Remote
Computer
3
c) Remote
422
3
d) Remote
STD
4
e) Manual
Operation
5
f) 1:2 Automatic mode
without
Priority
6
g) 1:2 Automatic mode with
Priority
7
h) 1:1 Automatic
mode
8
Fig. 1 Dip Switch Locations.
S1-S5
Settings
9
Fig. 2 PCB A3
10
Fig. 3 Remote connector J3
11
Types of
Faults
11
a)
N.O. and N.C. Defined
12
Priority leds and command
12
Setting Up Current
Monitoring
13
Monitoring Amplifier A current
with a volt
meter
15
Setting the DELTA
voltage
16
Fault
operation
18
Switch
Operation
19
Front Panel leds
20
Front Panel
Label
21
Factory
Settings
22
Notes
23
Appendix A (Computer
Protocol)
24
Appendix B
(Schematics)
25
Appendix C (Bias Tee
type)
26
Appendix D (Coax Switch
type)
27
Appendix E (Power supplies
type)
28
LOCAL
CONTROLLER – GENERAL DESCRIPTION
DNL-5 1:2
downlink controller
Rev-A
DNL-5
INFO.doc
1)
Capabilities and Functions
The DNL-5 is a
1:2 downlink amplifier controller.
Each Amplifier
is powered by its own power supply
(24v).
The controller
contains 3 LNB power supplies, 1
separate 28V switch power supply
(negative common on switches), 1
logic power supply, 2 co-ax
switches, 3 bias tees, low power
load, Universal AC inputs. TUV
Approved.
High quality
.141 Polycoat Semi Rigid cable used
internally.
Amplifier
current draw accessed via computer
port.
Two types of
fault inputs may be monitored.
1) Dry
contact closures where polarity may
be set via dip switch setting.
a.
Set S5-1 to “Off” for
normally open fault input.
(Closure=fault)
b.
Set S5-1 to “On” for normally
closed fault inputs. (Open =fault)
2)
Supply current being provided
by the controller. (See AMPLIFIER
CURRENT MONITORING SETUP later in
this document.)
Separate Fault
type enables:
a.
Set S5-2 to “On” to enable
dry contact fault inputs.
b.
Set S5-2 to “Off” to disable
dry contact fault inputs.
c.
Set S5-3 to “On” to enable
current monitoring faults
d.
Set S5-3 to “Off” to disable
current monitoring faults
The DNL-5 may
be used as a 1:1 controller. (Set
S4-1 to “On”)
User selectable
computer protocol.
(See Computer
Protocol later in this manual. Use
dip switches S1-S3….refer to Fig. 1)
Priority
Selection may be used to give one
amplifier preferential treatment in
automatic mode over the other.
Remote Dry
contact status indicators available
for [A-online, B-online, C-online,
Fault A, Fault B, Fault C, Manual,
Automatic, Local, Remote] Commands
for [S1,S2 switches, S3,S4 switches,
Manual select, Automatic select].
Front panel
display for Mode settings, RF path,
Amplifier Fault status, and Priority
setting.
Local
Mode: Local led is lit.
Refers to operating the controller
locally. Changing switch positions,
priority selection, and selection of
the control point (Locally or
Remote) is accomplished via the
front panel controls.
Remote
Computer: RS232/RS485 led lit.
Refers to
operating the controller via the
computer interface port. Changing
switch positions, priority
selection, system status, along with
various queries can be made via the
computer port.
Note: Queries
can be made from the computer port
at any time. In order to enter any
commands via the computer port, the
controller must be in Remote
RS232/485 mode.
See Appendix A
for computer Protocol information.
Remote
422: 422 led lit.
Refers to
operating the controller via a
remote panel that would be connected
to the RS422 port at the rear of
chassis. The remote panel is an
optional panel that may be used for
remote operation that has the same
appearance as the Local front
panel. The software that operates
this panel is proprietary to C&M
Systems. Contact factory for
availability of remote panels.
One handy local
use for the 422 port is as follows.
If it is desired to lock out all
front panel commands, simply place
the controller into remote 422.
Since the remote front panel doesn’t
exist, no commands will ever come
in, and no accidental control
changes can be inadvertently
entered.
Remote STD:
STD led lit.
Refers to
operating the controller via the
Remote STD port at the rear of
chassis. The indicators and
commands available at this port are
outlined on the Rear Chassis
Interconnect page (beginning of this
manual). The indicators are always
active and function during all
modes. The controller must be in
Remote STD mode in order to enter a
command via this port.
Note: Each
indicator relay that is mounted on
the main pcb has an associated led
mounted on the main pcb. A lit led
says that a command is going out to
the associated relay. A command out
to a relay closes the contacts on
the relay.

Please Note:
Pins 1,2,3,4
are open on J6.
However, if S1
supplies a second set of position
contacts on pins 7,8,9 (7-position 1
indicator, 8-indicator common,
9-position 2 indicator) on Rear
chassis J1, these position contacts
will show up on pins 1 and 2 on J6 (RMT
STD).
Likewise, if S3
supplies a second set of position
contacts on pins 7,8,9 (7-position 1
indicator, 8-indicator common,
9-position 2 indicator) on Rear
chassis J2, these position contacts
will show up on pins 3 and 4 on J6 (RMT
STD). indicator common is J6 pin 5.
Manual
mode: Manual led lit.
Refers to a
command being entered via some user
interface point of control. No
automatic switching takes place
while in manual mode. No priority
leds are lit while in manual mode.
( The exception to this is when the
controller is being operated in a
1:1 automatic configuration. While
in a 1:1 automatic configuration,
both priority leds are lit.)
Mode status and
Priority status is saved on internal
memory. The controller will
“remember’ the last status set.
1:2
Automatic mode without Priority:
Auto led lit. No Priority leds lit.
Operations in a
1:2 mode.
No manual
switch commands will be accepted by
the controller while in automatic
mode.
Priority
commands are permitted.
IMPORTANT
A FLASHING Auto
led signifies that the controller
cannot function in automatic. This
could be due to:
a)
Switches not being connected, (more
specifically, not reporting a
position.)
b)
The highest level of priority has
been met.
c)
The standby amplifier has a fault
condition.
Amplifier B is
always considered the backup
amplifier.
No priority
leds are lit when in Automatic.
1:2 Operation
without Priority:
To enter this
mode, both waveguide switches must
be in position 1. That means that
both amplifier A and amplifier C are
online, with amplifier B working
into a load.
In the event of
a failure on amplifier A, the
controller will switch S1 and S2 to
position 2. This will place
amplifier B online and terminate
amplifier A. At this point, the
automatic led will flash, indicating
that no further action with be taken
in automatic mode.
In the event of
a failure on amplifier C, the
controller will switch S3 and S4 to
position 2. This will place
amplifier B online and terminate
amplifier C. At this point, the
automatic led will flash, indicating
that no further action with be taken
in automatic mode.
In the event of
a failure on amplifier B (the back
up amplifier), the controller will
do no switching. At this point, the
automatic led will flash, indicating
that no further action with be taken
in automatic mode.
1:2
Automatic mode with Priority: Auto
led lit. Priority led lit.
Operations in a
1:2 mode.
While in
automatic, if an amplifier has
priority, the priority associated
with that amplifier will be lit.
Note that the back up amplifier
cannot have priority.
While in
automatic mode with priority,
everything from the previous section
applies to the operation of
automatic mode.
Here’s the
difference.
If a faulted
amplifier is backed up, and it is
not the priority amplifier, the
controller continues to function in
automatic. Should the priority
amplifier fail, amplifier B changes
the switches in order to backup the
priority amplifier. When the
priority amplifier has been placed
online, then automatic has reached
then end of its cycle.
Example of
automatic with priority on C:
Amplifier C has
priority.
All switches
are in position 1.
No faults
exist.
Amplifier A
fails…..S1, and S2 go to position
2…..placing amplifier B online.
Should
Amplifier C fail, Then
Amplifier C
fails,,,,,,S1 and S2 go to position
1, S3 and S4 go to position
2…..placing amplifier B online
backing up amplifier C.
Example of
automatic with priority on A:
Amplifier A has
priority.
All switches
are in position 1.
No faults
exist.
Amplifier C
fails…..S3, and S4 go to position
2…..placing amplifier B online.
Should
Amplifier A fail, Then
Amplifier A
fails,,,,,,S1 and S2 go to position
2, S3 and S4 go to position
1…..placing amplifier B online
backing up amplifier A.
1:1
Automatic mode: Auto led lit. Both
priority leds lit.
For 1:1 mode
operations.
No manual
switch commands will be accepted by
the controller while in automatic
mode.
Priority
commands are not permitted.
IMPORTANT
A FLASHING Auto
led signifies that the controller
cannot function in automatic. This
could be due to:
a) Wave guide Switches not
connected, (more specifically, not
reporting a position.)
b)
The standby amplifier has a fault
condition
The DNL-5
controller can be used as a 1:1
controller by setting dip switch
S4-1 to the “ON” position. With
this setting, only the positions of
S1 and S2, along with the fault
status of amplifier A and amplifier
B are displayed on the front panel.
Also illuminated are BOTH priority
leds.
Both priority
leds being lit simply signifies that
the controller is in a 1:1 mode.
There is no “priority” in the 1:1
mode per se.
The automatic
operation of the DNL-5 while in the
1:1 mode is as follows:
The online
amplifier (amplifier transmitting
out) will be backed up by the
amplifier that is being terminated.
The controller will remain in
automatic mode (no blinking
automatic led) as long as both
amplifier are in a no fault
condition.
If a failed
amplifier gets backed up by the
“other” amplifier, and then later
recovers, it then becomes the backup
amplifier and automatic resumes
(automatically).
FIG. 1

Right Side Of
Main PCB. Note Dip Switch
Locations.
Pay close
attention to orientation and Pin 1
on Dip Switches.
Switch 1 is
located near Pin 1 on all dip
switches.
S1-S3 used for
Computer Protocol setup.
S4-1 “Off”
for 1:2 operation.
S4-1 “On”
for 1:1 operation.
S5-1: “Off”
for normally open fault inputs.
(closure for a fault)
S5-1: “On”
for normally closed fault inputs.
(open for a fault)
S5-2: “Off”
ignore closure fault inputs.
S5-2: “On”
Monitors fault inputs.
S5-3: “Off”
Do not monitors amplifier current
levels S5-3: “Off”.
S5-3: “On”
Monitor amplifier current levels for
faults. (outside “window” causes
fault)
(monitored
faults effect automatic function)
FIG. 2 PCB
3……..Analog PCB.

PCB A3 is
mounted on top of the right side of
main PCB A1.
Types of
Faults:
The DNL-5 has
provisions for monitoring 2 types of
fault inputs.
One type of
fault is a contact closure fault
input. This is typically input from
a fault relay from the amplifier (or
any other device in the chain).
These fault
inputs are fed into the controller
through the rear chassis D-Sub type
(Soc) connector J3. Two pins are
allocated for each amplifier.
FIG. 3
These fault
inputs may be configured via a dip
switch setting for either a
“normally open” or “normally closed”
fault input.
Dip switch 5 is
used for this selection.
Dip switch 5 is
a 3 position dip switch.
Set S5-1 to
“On” for normally closed fault
input. (Open=fault)
Set S5-1 to
“Off” for normally open fault
inputs. (Closure =fault)
Set S5-2 to
“On” in order to monitor the contact
fault inputs.
Set S5-2 to
“Off” in order to ignore the contact
fault inputs.
Normally
open fault defined:
A normally open
fault input is defined by this
document as a fault input that is
“normally open” in a no fault
condition. When the “normally open”
fault input closes, a fault is
declared. A closure causes a fault.
Normally
closed fault defined:
A normally
closed fault input is defined by
this document as a fault input that
is “normally closed” in a no fault
condition. When the “normally
closed” fault input opens, a fault
is declared. These two fault pins
being open (no contact with each
other) constitutes a fault
condition.
Priority
leds and command:
IMPORTANT:
Priority leds / Priority
command push button are only
illuminated/active during
an automatic mode of operation.
A priority
command may only be entered while
the unit is in automatic.
Both Priority
leds being lit identify the unit as
a 1:1 controller.
In 1:2
automatic operation, either one or
none of the priority status leds are
on.
Priority status
is stored in EEPROM.
Current
Monitoring Faults:
Setting Up
Current Monitoring:
When the
amplifier is ON, it should be
drawing current from a supply inside
the controller. This current is
monitored in such a way, that should
it deviate from a specified window,
a fault is declared.
See fig. 2 for
PCB layout.
Setting Up the
current monitoring feature:
Set Dip switch
5-3 to “ON”. (Factory set to “On”)
This will
instruct the DNL-5 to monitor the
currents being drawn from the
amplifiers. This monitoring will
affect automatic function.
When an
amplifier operates outside its
window for more than a few seconds,
a fault is declared. This fault
will show up on the front panel by
the associated fault led turning
from green to a flashing red.
In order to set
up an amplifier, a minimal amount of
adjustments must be made. These
adjustments allow the DLN-5 to be
used with just about any amplifier.
The adjustments are necessary
because different amplifiers draw a
different amount of current.
For amplifiers
that draw >325mA (More than 0.325
Amps), Go to Section 1.2.
(no need to
move any jumpers if your amplifiers
draw less than 325 mA. @ 24V.)
(The DNL-5 is
shipped from the factory, assuming
that all 3 amplifiers are going to
draw less than 325 mA each.)
Section 1.1
(See fig. 2)
All that really
needs to be done is, with an
amplifier ON and drawing current,
set it’s associated “V Adj”
potentiometer to 2.5V. This is done
using potentiometers R3, R11, and
R19, for amplifiers A,B,C
respectively. This voltage may be
monitored on test points TP1,TP3,TP5
for amplifiers A,B,C respectively.
Amplifier A:
With a volt
meter set up between TP1 (SET 2.5V)
and GND (REF pin), measure the
voltage being displayed with
amplifier A drawing current. Rotate
potentiometer R3 so that the volt
meter reads about 2.5V.
Setting
Amplifier B:
With a volt
meter set up between TP3 (SET 2.5V)
and GND (REF pin), measure the
voltage being displayed with
amplifier B drawing current. Rotate
potentiometer R11 so that the volt
meter reads about 2.5V.
Setting
Amplifier C:
With a volt
meter set up between TP5 (SET 2.5V)
and GND (REF pin), measure the
voltage being displayed with
amplifier C drawing current. Rotate
potentiometer R19 so that the volt
meter reads about 2.5V.
With an
amplifier drawing current, and its V
ADJ voltage set at 2.5V, the front
panel led should be green.
The current
being drawn by the amplifiers may be
monitored using a Volt meter. The
current being drawn is transformed
into a voltage that may be measured
on TP2, TP4, TP6, for amplifiers
A,B,C respectively.
Monitoring
Amplifier A current with a volt
meter:
With a volt
meter set up between TP2 (CURRENT
MONITOR VOLTAGE)) and GND (REF
pin), measure the voltage being
displayed with amplifier A drawing
current. Set the volt meter to
measure VOLTS. This allows a
measurement of the current in terms
of a voltage. As an example, a
measurement of 0.230 dcV may be
interpreted as Amplifier A drawing
230 mA or (0.230 Amps).
Monitoring
Amplifier B current with a volt
meter:
With a volt
meter set up between TP4 (CURRENT
MONITOR VOLTAGE)) and GND (REF
pin), measure the voltage being
displayed with amplifier B drawing
current. Set the volt meter to
measure VOLTS. This allows a
measurement of the current in terms
of a voltage. As an example, a
measurement of 0.230 dcV may be
interpreted as Amplifier B drawing
190 mA or (0.190 Amps).
Monitoring
Amplifier C current with a volt
meter:
With a volt
meter set up between TP6 (CURRENT
MONITOR VOLTAGE)) and GND (REF
pin), measure the voltage being
displayed with amplifier C drawing
current. Set the volt meter to
measure VOLTS. This allows a
measurement of the current in terms
of a voltage. As an example, a
measurement of 0.230 dcV may be
interpreted as Amplifier C drawing
270 mA or (0.270 Amps).
Setting the
DELTA voltage:
(IMPORTANT:
Please note there should not be any
need to adjust the potentiometer R25
(DELTA V).
What is “DELTA
V”?
The value of
“DELTA V” is what sets up the window
around the 2.5V. This value set up
by potentiometer R25 may be measured
at TP7. Typically, the value of
this “DELT V” is around 0.5V. It is
set at the factory at 0.6. The
window may be expanded or contracted
if desired.
A current
monitored fault is declared when the
current being monitored falls
outside the “window”. The “window”
is between 2.5V - DELTA V and 2.5V +
DELTA V.
Please Note
that the amplifier currents are
available on the computer port, but
these measurements mustn’t be used
for any fine measurement purposes.
The A/D converter used on the DNL-5
is an 8-bit device. That means that
each bit is worth 20 mV. There is a
1:1 relationship between current and
voltage with this application, so
each bit is worth 20 mA of current.
Therefore, the measurements
available on the computer interface
port are to be viewed as somewhat
coarse numbers only.
Current
Monitoring Set up for Amplifiers
that draw more than 325 mA.
Section 1.1
(See fig. 2)
For amplifiers
that draw more than 325mA, it’s
necessary to move the Jumpers at
JP1,JP2 for amplifier A, JP3,JP4 for
amplifier B, and JP5,JP6 for
amplifier C.
As you can see
viewing FIG. 2, the Jumper locations
have 3 pins. The top two pins
should be jumped for amplifiers
drawing >300 mA (or 325mA), and for
amplifiers that draw less than 300
mA (or 325mA), the bottom two pin
should be jumped.
There is no
need to use SW1 on A3.
Fault
operation:
When an
amplifier is in a no fault
condition, its associated led should
be green on the front panel and the
relay indicator on the remote STD
port should be open.
In the event of
a fault, the fault led will go red,
and begin to flash on and off. The
audible alarm on the front panel
will sound on and off (if the
audible enable switch is placed to
“ON”). The relay fault indicator on
the remote STD port will become a
steady closure.
Pushing the
“RESET” button on the front panel
will extinguish the audible alarm,
and cause the fault led to go steady
state. The fault light will always
track the true status of the fault.
A blinking green led may signify
that a fault had occurred, but then
went away.
The response
time to a closure type fault is
immediate. (keep in mind the time
needed to switch a wave guide
switch.)
The response
time to a current fault is a few
seconds. This allows any minor
variations that may occur in the
amplifier current draw to take place
without causing an alarm.
Switch
Operation:
The DNL-5
contains two coax switches. They
have the designation of S2 and S4 on
the front panel.
The two wave
guide switches (not normally
supplied) are external to the
controller.
The S1 S2
combination of input and output
switches are electrically ganged.
This means that the position
commands are sent out to the 2
switches at the same time, from the
same source. Whenever the
controller switches S1 to a
position, the input coax switch that
is internal to the controller will
receive the same position command.
That is why it is necessary for the
wave guide switches and the coax
switches to have the same switching
voltage and polarity.
For most
applications it is assumed that the
operating voltage of the switches is
between 20-30Vdc, with the switch
common being “Negative”. That means
that the command voltage is
“positive”. The DNL-5 uses a 28Vdc
supply for switch operation to
reduce the effects of cable losses
due to length and gauge of the
switch cables being used.
Position
Indicators are different.
Each of the 4
switches in the system have two
position indicators (position 1 and
position 2 indicators). Each of
these indicators are independently
displayed on the front panel. Under
normal operation, both the input and
output switches will always be in
the same position. It should be
noted that for automatic switching
purposes, the position indicators
from the waveguide switch are used.
Should the
input wave guide switch and output
coax switches be in different
positions, those positions will be
displayed on the front panel.
All coax
switches used are of the “Latching”
type. This means that the switches
maintain their position in the event
of the controller being turned off.
All commands
out to the switches are of a
momentary nature. A command only
exists for about 0.5 seconds. This
facilitates the use of the
mechanical override knobs that may
be present on the switches.
All switches
are 4 port devices. When a switch
has a position, then two diagonally
opposite leds should be lit on the
front panel at the same time. A
front panel switch display (the 4
leds), should always have 2 opposite
leds lit. Of course if the switch
is not connected, then all leds
should be “off”.
Also Note that
there are 4 command relays on the
main pcb. Relays K1 (position 1)
and K2 (position 2) are used to
drive S1 (external wave guide
switch) and S2 (internal coax
switch). Relays K3 (position 1)
and K4 (position 2) are used to
drive S3 (external wave guide
switch) and S4 (internal coax
switch). There are leds mounted on
the main pcb that are associated
with each command relay. A relay is
receiving a command as long as the
associated led is lit.
NOTE:
With all
switches in Position 1, Amplifier A
and Amplifier C are online.
Led Test
Command:
Pressing the
led test button on the front panel
should illuminate all of the leds on
the front panel. The Bi-colored leds
will appear an orange color. (This
is the led going from green to red
to green very quickly). The only
Bi-colored leds on the front panel
are the fault leds. The rest of the
front panel leds operate as a single
color.
Note: The front
panel led test command has no effect
on leds mounted on the main pcb
inside the controller. Those leds
indicate active commands going out
to a particular relay.
Audible
Alarm:
The audible
alarm will sound whenever a new
alarm occurs. It sounds whenever a
fault led is flashing. It can be
disabled by using the Audio on/off
switch. If an alarm occurs and the
alarm sounds, pressing the fault
reset button will turn off the
alarm.
Fault Leds:
A fault led is
associated with each LNB. See
explanation of function earlier in
this document.
Mode leds:
The mode leds
(when lit) represent the mode the
controller is in at the time. Either
auto or manual led should be lit at
one time. Also, only one of the
remote or local leds should be lit
at one time.
Front Panel
Label:
The front panel
area above the control area, where
the local/remote, auto/manual
switches are, is purposely left
blank so the end user can place his
own identification for the panels
place in the over all system. This
can be done by using a simple label
maker with an adhesive backing.
If you don’t
have a label maker, C&M Systems will
make one free of charge if the exact
text is supplied, and it is of
reasonable physical length.
Factory
Settings for pcb A1:
S1,S2,S3 are
used for computer interface.
They have been
set up at the factory as follows.
Address = “A”
BAUD
= 9600
{}
message delimiters
Check Sum check byte returned
No
parity
RS485 mode
Ignore bad Checksum
No
CR or LF returned
Termination resistor not engaged
Therefore, 7 bit words.
S4-1 “Off”
for 1:2 operation.
S5-1: “Off”
for normally open fault inputs.
(closure for a fault)
S5-2: “Off”
ignore closure fault inputs.
S5-3: “On”
Monitor amplifier current levels for
faults.
Factory
Settings for pcb A3:
The DNL-5
assumes that all amplifiers draw
less than 325 mA.
Therefore all
Jumpers on A3 (The top analog pcb
above A1 (main pcb)) are positioned
accordingly.
Delta V set at
0.6 volts.
The “2.5V”
potentiometer settings were set with
a current draw of 240 mA.
Appendix A
Appendix B
Appendix C
Appendix D
Appendix E
|